Appendix
Manual ERZ 2000-NG · EN07 · 2019, May 13th
409
.J.2.2
Modbus EGO
This is a special interface for
Erdgas Ostschweiz.
EGO-specific Modbus registers
are:
Register
Data type
Column
Group
Value
Value
Bytes
Access Line
Description
(Display)
(Modbus)
2000 4
unsigned integer 32-bit
R
IP 1
EGO-Modbus
Vn totalizer
4044123 m3
00 3D B5 5B
2002 4
unsigned integer 32-bit
R
IP 2
EGO-Modbus
Vb totalizer
114962 m3
00 01 C1 12
2004 4
unsigned integer 32-bit
R
IP 3
EGO-Modbus
Energy totalizer
57809 MWh
00 00 E1 D1
2006 4
unsigned integer 32-bit
R
IP 4
EGO-Modbus
Vn dist. totalizer
675679 m3
00 0A 4F 5F
2008 4
unsigned integer 32-bit
R
IP 5
EGO-Modbus
Vb dist. totalizer
18095 m3
00 00 46 AF
2010 4
unsigned integer 32-bit
R
IP 6
EGO-Modbus Energy dist. totalizer
7132 MWh
00 00 1B DC
2012 4 float IEEE 754
R
IP 7
EGO-Modbus
Vn flow rate
6779.9 m3/h
45 D3 DF 5A
2014 4 float IEEE 754
R
IP 8
EGO-Modbus
Vb flow rate
151.0 m3/h
43 17 06 FA
2016 4 float IEEE 754
R
IP 9
EGO-Modbus Energy flow rate
81359.0 kW
47 9E E7 84
2018 4 float IEEE 754
R/W IP 10
EGO-Modbus
Standard density
0.80 kg/m3
3F 4C CC CD
2020 4 float IEEE 754
R/W IP 11
EGO-Modbus
Calorific value
12.0 kWh/m3
41 40 00 00
2022 4 float IEEE 754
R/W IP 12
EGO-Modbus
Hydrogen
0.0 mol-%
00 00 00 00
2024 4 float IEEE 754
R/W IP 13
EGO-Modbus
Carbon dioxide
1.02 mol-%
3F 82 9C BC
2026 4 float IEEE 754
R
IP 14
EGO-Modbus
Operating density 35.9 kg/m3
42 0F A7 8C
2028 4 float IEEE 754
R
IP 15
EGO-Modbus
Absolute pressure 42.000 bar
42 28 00 00
2030 4 float IEEE 754
R
IP 16
EGO-Modbus
Temperature
10.00 °C
41 20 00 00
2032 2
unsigned integer 16-bit
R
IP 17
EGO-Modbus
alarm
0
00 00
Important points
x
The ERZ2000-NG is a Modbus slave.
x
Supported function codes:
03
Read holding register
Read data
16
Preset multiple registers
Write data
x
The register addresses are referenced to 0 (zero).
If, for example, register 2000 is queried on the interface, coordinate
IB17 Register offset
= "0" must be parameterized.
x
Totalizers and disturbance totalizers correspond to billing mode 1.
x
Standard density, calorific value, hydrogen and carbon monoxide can be
described via Modbus.
In order to ensure that the values are used for conversion, the operating
mode of the corresponding measurement input must be parameterized to
EGO Modbus.
x
There is no special EGO interface operating mode.
x
EGO mode only works advantageously with GERG 88.
x
EGO mode does not work with billing mode 2, 3, 4.
Summary of Contents for ERZ2000-NG
Page 10: ......
Page 68: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 58 Figure 44 Menu LA Overview...
Page 69: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 59 Figure 45 Menu LB Totalizer BM1...
Page 77: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 67 Figure 51 Overview System sub menu...
Page 241: ...6 Flow meters Manual ERZ 2000 NG EN07 2019 May 13th 231 Figure 167 Interface module C34...
Page 340: ...8 Overview Coordinates Manual ERZ 2000 NG EN07 2019 May 13th 330 8 5 6 TSV export...
Page 453: ...Certificates Manual ERZ 2000 NG EN07 2019 May 13th 443...