3 Electrical connections
Manual ERZ 2000-NG · EN07 · 2019, May 13th
116
Example for a setting
The setting must be made in the menu
IE DSfG Remote data transmission access
:
IE06 Modem init. string
ate0s0=1
IE07 Dial prefix
atx3dt
Figure 86: DSfG data transmission
Meaning:
at
Prefix of a command line
e0
Echo function deactivated
s0=1 Set register 0 to 1, which means the number of alert characters after which the
modem answers and establishes the connection, should be 1.
x3
Response setting:
Hayes Smartmode 300 compatible answers / blind dialing (extension)
plus all CONNECT answers
plus recognition of busy symbols
dt
sound selection process (dp = pulse selection process)
If a different modem is used, there may be other commands, which are covered in
the manufacturer's manual.
Additional settings in the menu
IB Serial interfaces
: