3 Electrical connections
Manual ERZ 2000-NG · EN07 · 2019, May 13th
114
COM 5 (modem)
Pin assignment
Pin
Mode: RS 232
1
DCD
2
RxD
3
TxD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
RI
Use
RS 232 with handshake plus carrier plus ring. Usable for MODEM (DFÜ).
With connection of a modem, "Modem" must be selected in coordinate
IB21 COM 5
operating mode
.
3.1.6
External modem connection
1. The COM 5 interface is used for connection.
2. Modem type
The Phoenix industrial modem, type PSI-DATA/FAX-Modem/RS232, is the
standard unit