7 Parameter of the gas
Manual ERZ 2000-NG · EN07 · 2019, May 13th
312
+
A96-7 Hs GC timeout Calorific value sensor communication error
and the calorific value switches to the default value. If the bus plug is re-inserted, the
alarm goes with the next bus telegram and the calorific value shows the current RMG
bus value.
Processing 24 Components
Newer gas analysis devices, such as the GC 9300, deliver significantly more analysis
data than, for example, the older GC 9000. In order to import up to 24 gas compo-
nents in the ERZ2000-NG via RMG bus, the appropriate operating mode must be
parameterized on COM 4.
IB Serial interfaces
Access Line
Name
Value
Unit
B
12 COM4 Operating mode
Note
For re-use of the imported data, e.g. in the calorific value input, RMG bus must
be the setting for the operating mode. There is no special 24K parameterization
for the measurement inputs.
AD Calorific value
A § 1 Measurement variable
11.350
kWh/m3
A § 2 Input value ->
IH03
11.350
kWh/m3
E § 3 Operating mode
RMG-Bus-24K
RMG-Bus
Summary of Contents for ERZ2000-NG
Page 10: ......
Page 68: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 58 Figure 44 Menu LA Overview...
Page 69: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 59 Figure 45 Menu LB Totalizer BM1...
Page 77: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 67 Figure 51 Overview System sub menu...
Page 241: ...6 Flow meters Manual ERZ 2000 NG EN07 2019 May 13th 231 Figure 167 Interface module C34...
Page 340: ...8 Overview Coordinates Manual ERZ 2000 NG EN07 2019 May 13th 330 8 5 6 TSV export...
Page 453: ...Certificates Manual ERZ 2000 NG EN07 2019 May 13th 443...