![background image](http://html1.mh-extra.com/html/rmg/erz2000-ng/erz2000-ng_operating-manual_1467424359.webp)
9 Faults
Manual ERZ 2000-NG · EN07 · 2019, May 13th
349
487 A(R) 92-4
HART3 failure
HART 3 input failed
2 No
No
488 A(R) 92-5
HART4 failure
HART 4 input failed
2 No
No
489 A(R) 92-6
HART5 failure
HART 5 input failed
2 No
No
490 A(R) 92-7
HART6 failure
HART 6 input failed
2 No
No
491 A(R) 92-8
Corrupt param.
corrupted parameter detected
1 No
No
492 A(R) 93-0
Def.cont.inp.
Contact input failed
2 No
No
493 H
93-1
Hscorr>perm.(N)
Ongoing Hs correction value formation out of permitted range
2 Yes No
494 H
93-2
Sd corr>perm.(N)
Ongoing Sd correction value formation out of permitted range
2 Yes No
495 H
93-3
Function test
A function test is running at the moment
2 No
No
496 H
93-4
USZ implaus.
USZ transmitter, implausible protocol data
2 No
No
497 A
93-5
USZ alarm
USZ transmitter signalizes an alarm
2 No
No
498 A
93-6
USZ timeout
No more signal from USZ transmitter
2 No
No
499 H
93-7
Vo1 implaus.
USZ totalizer for Vo1 shows implausible behavior
1 No
No
500 H
93-8
Vo2 implaus.
USZ totalizer for Vo2 shows implausible behavior
1 No
No
501 H
93-9
Vo1D implaus.
USZ totalizer for Vo1D shows implausible behavior
1 No
No
502 H
94-0
Vo2D implaus.
USZ totalizer for Vo2D shows implausible behavior
1 No
No
503 H
94-1
Time sync.para.
Parameterization of time synchronization implausible
2 No
No
504 A(R) 94-2
I9 failure
Current measurement 9 failed
2 No
No
505 A(R) 94-3
I10 failure
Current measurement 10 failed
2 No
No
506 A(R) 94-4
I11 failure
Current measurement 11 failed
2 No
No
507 A(R) 94-5
I12 failure
Current measurement 12 failed
2 No
No
508 A(R) 94-6
PT3 failure
Resistance measurement 3 failed
2 No
No
509 A(R) 94-7
PT4 failure
Resistance measurement 4 failed
2 No
No
510 A(R) 95-0
Math.problem
Mathematical error
1 Yes No
511 A
95-1
Corrupt code
corrupt code detected
1 No
No
512 A
95-2
Alarm volume
hard-wired contact of volume transmitter shows alarm
2 No
No
513 W
95-3
Warning volume
hard-wired contact of volume transmitter shows warning
2 No
No
514 W
95-4
Time sync fail
Time synchronization failed
1 No
No
515 H
95-5
Net time error
Net time error
1 No
No
516 A(R) 95-6
HART9 failure
HART 9 input failed
2 No
No
517 A(R) 95-7
HART10 failure
HART 10 input failed
2 No
No
518 A(R) 95-8
HART11 failure
HART 11 input failed
2 No
No
519 A(R) 95-9
HART12 failure
HART 12 input failed
2
No
No
520 A
96-0
rd loss
Loss of relative density
2 Yes No
521 A
96-1
rd<l.alarm lim.
Relative density below lower alarm limit
2 Yes Yes
522 A
96-2
rd>up.alarm lim.
Relative density exceeds upper alarm limit
2 Yes Yes
523 A
96-3
rd jump
Relative density gradient exceeds maximum
2 Yes Yes
524 W
96-4
rd<l.warn.lim.
Relative density below lower warning limit
2 Yes Yes
525 W
96-5
rd>up.warn.lim.
Relative density exceeds upper warning limit
2 Yes Yes
526 H
96-6
rd param.error
Inconsistent parameterization, relative density
1 No
No
527 A
96-7
Hs GC timeout
No more signal from the superior calorific value transmitter
2 Yes No
528 A
96-8
sd GC timeout
No more signal from standard density transmitter
2 Yes No
529 A
96-9
rd GC timeout
No more signal from relative density transmitter
2 Yes No
530 A
97-0
CO2 GC timeout
No more signal from CO2 transmitter
2
Yes
No
531 A
97-1
N2 GC timeout
No more signal from N2 transmitter
2 Yes No
532 A
97-2
H2 GC timeout
No more signal from H2 transmitter
2 Yes No
533 A
97-3
Hs GC alarm
GC reports loss of superior calorific value
2 Yes No
534 A
97-4
sd GC alarm
GC reports loss of standard density
2 Yes No
535 A
97-5
rd GC alarm
GC reports loss of relative density
2 Yes No
536 A
97-6
CO2 GC alarm
GC reports loss of carbon dioxide
2 Yes No
Summary of Contents for ERZ2000-NG
Page 10: ......
Page 68: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 58 Figure 44 Menu LA Overview...
Page 69: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 59 Figure 45 Menu LB Totalizer BM1...
Page 77: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 67 Figure 51 Overview System sub menu...
Page 241: ...6 Flow meters Manual ERZ 2000 NG EN07 2019 May 13th 231 Figure 167 Interface module C34...
Page 340: ...8 Overview Coordinates Manual ERZ 2000 NG EN07 2019 May 13th 330 8 5 6 TSV export...
Page 453: ...Certificates Manual ERZ 2000 NG EN07 2019 May 13th 443...