6 Flow meters
Manual ERZ 2000-NG · EN07 · 2019, May 13th
248
6.5.1
GA Tube dimensions
Figure 183: Menu GA Tube dimensions
Menu GA Tube dimensions
enables settings of the orifice plate parameters (for the
ERZ2014-NG, ERZ2114-NG, ERZ2012-NG and ERZ2112-NG).
The neck is defined at 20°C in coordinates GA07 and GA08.
The temperature correction of the orifice plate diameter and the inside pipe diameter
takes place in accordance with VDI/VDE 2040, sheet 2 (chapter 10) of April 1987.
There are two calculation methods, one of which is based on the linear heat expan-
sion coefficient and the other is based on a proximity equation with coefficient selec-
tion depending on the materials for the orifice plate and pipe, which can be adjusted
in coordinates GA10 and GA11. The following table shows the selection options.