4 Communication and bus systems
Manual ERZ 2000-NG · EN07 · 2019, May 13th
169
Coordinate
IF06 DSfG fault
is an auxiliary quantity for the information transport of the
lower DSfG protocol layers for fault evaluation. If parameter
JD01
Software debug
is
set to "yes", the following messages are activated:
x
H64-6 DSfG unex char.: unexpected characters in telegram
x
H64-7 DSfG overflow:
Input buffer overflow
x
H64-8 DSfG checksum: Block check incorrect
x
H64-9 DSfG broadcast:
Block check in broadcast incorrect
x
H65-0 DSfG broadc_inc.: Broadcast ignored
x
H65-1 DSfG busterM,m.: Bus termination problem
Note
The cause of the messages may lie in the device in question or another
bus participant. The device that displays the message does not necessari-
ly have to be the cause.
Coordinates
IF07 User pattern
and
IF08 Address pattern
are auxiliary quantities for
the bit pattern; each bit corresponds to an external (
IF07
) or internal (
IF08
) partici-
pant. The least significant big is DSfG address "A". Together with
IF06
,
IF01
is
formed.
Summary of Contents for ERZ2000-NG
Page 10: ......
Page 68: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 58 Figure 44 Menu LA Overview...
Page 69: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 59 Figure 45 Menu LB Totalizer BM1...
Page 77: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 67 Figure 51 Overview System sub menu...
Page 241: ...6 Flow meters Manual ERZ 2000 NG EN07 2019 May 13th 231 Figure 167 Interface module C34...
Page 340: ...8 Overview Coordinates Manual ERZ 2000 NG EN07 2019 May 13th 330 8 5 6 TSV export...
Page 453: ...Certificates Manual ERZ 2000 NG EN07 2019 May 13th 443...