Chapter 5 Parameter Setting Description
111
5
2.In multi-pump control systems, drives will start / cut off the operation in accordance with
below diagram.
Time
#0
#0
#0
#1
Drive #1
Drive #0
F_135
Drives Standby
Numbers of
Multi-pumps Control
system
․
In multi-pump control systems, setting the number
of drives standing by.
*According to the condition of applications, users can set
the standing by number of drives to protect the system.
*Setting range: 0~3 units.(0: disable)
*The default parallel number of drives are 2 sets.
*Valid setting of standing by drives as below.
F_150
Continuous Water
Supply Control
0:Disable
1: Enable(default)
F_151
Less Pumps set during
Operation
In multi-pump control systems, deploying the number of
operating pumps and maintaining the system pressure
within certain acceptable limits.
Setting range: 0~1 pump (0: Disable ; Default value: 1
pump)