Chapter 5 Parameter Setting Description
103
5
F_092
Parameter Setting Lock
0: Parameters are changeable.
1: Parameters are locked.
2&3: Reversed
※
According F_004 setting to change selection of setting value (SV)
F_093
Automatic Voltage Regulation (AVR)
0: Disable
1: Enable
F_095
Power Source
The setting value according to the actual power source voltage.
200V series setting range: 190.0 ~ 240.0V;
400V series setting range: 340.0 ~ 480.0V.
When the drive is power ON for first time and the power source voltage is lower than the
90%
of F_095 setting value, the drive will display ―LE‖ warning message.
After the power ON for drive, the drive displays ―LE‖ message when the power source is
lower than the 70% of F_095 setting value.
F_098
Grounding Fault Protection (GF)
0: Disable
1: Enable
F_097
Digital Input Response Time
Range: 1~16ms (default: 10ms)
If the signal length of digital inputs is smaller than the digital input response time, drive
software will reject the input signal and do no process to input signal.
F_193
Decrease the Switching Frequency
0: If the drive is overloaded, the swithing frequency can not be adjusted with amount of
current.
1: If the drive is overloaded, the switching frequency can be adjusted with amount of
current.