Attachment 2 Default Value List
180
Att.2
Attachment 2 Default Value List
Func.
Name
dEF 60 dEF 50 dEF 52 dEF 53 dEF 57
F_000
Drive Information
-
-
-
-
-
F_001
Start Command Selection
3
3
3
3
3
F_002
Frequency
Command Selection
1
2
2
2
2
F_003
Selection
of ―STOP‖ Key
Validity
1
1
1
1
1
F_004
Setting Value
(SV)
Selection
1
1
1
1
1
F_005
Auto-Storing of Setting Value
Selection
1
1
1
1
1
F_006
Selection of Main Display
1
7
7
7
7
F_007 Pressure Transducer Setting
10.0
10.0
10.0
10.0
10.0
F_008
Maximum Allowabel
Operating Pressure
100
100
100
100
100
F_009
Starting Frequency
0.5
0.5
0.5
0.5
0.5
F_010
Starting Voltage
8.0
8.0
8.0
8.0
8.0
F_011
Base Frequency
60.0
60.0
60.0
50.0
60.0
F_012
Base Voltage
220.0
220.0
220.0
220.0
220.0
F_013
Selection of Pump Shift
Operation
(Parallel control)
3
3
3
3
3
F_015
Control Mode Selection
(Parallel control)
0
1
2
1
5
F_016
Set Drive’s No. for
Parallel Control
0
0
0
0
0
F_017 Maximum Output Frequency
60.0
60.0
60.0
50.0
60.0
F_018
Reference Frequency of
Accel/Decel Time
60.00
60.00
60.0
50.00
60.00
F_019
Primary Acceleration Time
5.0
3.0
3.0
3.0
1.0
F_020
Primary Deceleration Time
5.0
3.0
3.0
3.0
1.0
F_021
Launch Detection Time
(Parallel Control)
6.0
6.0
6.0
6.0
6.0
F_022
Launch Detection Level
(Parallel Control)
0.4
0.4
0.4
0.4
0.4
F_023
Cut-off Frequency
(Parallel Control)
50.0
50.0
50.0
42.0
50.0