Chapter 4 Parameter List
61
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_071
Stall
Prevention
Level at
Constant
Speed
While the stall is occurred during constant
speed running condition, the prevention of
stall is to decrease the speed of motor.
30%~200%
of drive
rated
current
1%
130
F_072
Acceleration
Time for
Stall
Prevention
during
Constant
Speed
Set the acceleration time to recover to the
constant speed from stall prevention.
0.1~
3200.0
0.1
sec
3.0
(note3)
F_073
Deceleration
Time for
Stall
Prevention
during
Constant
Speed
Set the deceleration time to recover to the
constant speed from stall prevention
0.1~
3200.0
0.1
sec
3.0
(note3)
F_074
Stall
Prevention
Setting at
Deceleration
0: Disable
1: Enable
0, 1
─
1
F_075
DC Braking
Level
Set the current level of DC braking.
0~150%
of drive
rated
current
1%
50
F_076
Time
Interval of
DC Braking
at Stop
Set the time for DC braking after drive
stopped.
0.0~20.0
0.1
sec
0.2
F_077
Time
Interval of
DC Braking
at Start
Set the time for DC braking before drive
starts.
0.0~20.0
0.1
sec
0.0
F_078
Operation
Selection at
Instantane-
ous Power
Failure
0: Drive cannot be restarted
1: Drive can be restarted
0~1
─
0
F_079
Auto-
Restarting
Selection for
Error Trip
Condition
0: Short time interval to auto-restart according
to the setting of F_080 (OC,OE,GF only).
1: Long time interval to auto-restart according
to the setting value of F_080, F_083 (all
errors except Fb Lo).
0~1
─
1
F_080
Maximum
Reset Time
of
Auto-Restart
at Drive’s
Error Trip
Set the counting number for drive auto-restart
when errors occur.
0~16
1
10
F_081
Switching
Frequency
The setting value is higher and the motor
noise is lower.
0~6
─
6
(note4)
F_082
Stop Mode
0: Ramp to stop
1: Coast to stop
2: Coast to stop + DC braking
0~2
─
0