Chapter 5 Parameter Setting Description
77
5
F_006
KP-605 Selection of Main Display
In the monitor mode, there are 8 monitor modes can be selected. The corresponding
value and monitor modes are shown as below table:
1. Output Frequency
2. Frequency Command
3. Output Voltage
4. DC bus Voltage
5. Output Current
6. Terminals Status & Temperature
7. Setting Value & Practical Value (default value)
F_099
External Indicator 1
F_100
External Indicator 2
F_101
External Indicator 3
1. External indicator (DM-501) is used for expanding the display of
―monitor mode‖.
DM-501 can be directly connected to the drive without connecting other power source.
2. The setting range of F_099 ~ F_101 is 0 ~ 6, and the significance is shown as below:
0: Disable the indicator
1: Output frequency
2: Frequency command
3: Output voltage
4: DC bus voltage
5: Output current
6: Terminal status and heat sink temperature
※
DM-501 cannot monitor the pressure setting and actual pressure
3. Please select twisted-pair shield wiring and shielding connected to the GND terminal
of drive
’s control board.
4. The wiring diagram of external indicators is as follows:
5
CN1
1
Indicator 1 (DM-501)
RM6F5 control
board
Indicator 2 (DM-501)
Indicator 3 (DM-501)
GND
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
5.The position of connector (CN1), please refer to
―2-3-5 Control Board‖ on page 26,27.