Chapter 2 Installation and Confirmation
34
2
f. CN2 / CN3: KP-605 (RJ-45) / Modbus RS-485 Modbus Port
8 1
Type
Pin
Function
Description
Modbus(RS-485)/
KP-605
communication
1
Communication
transmission terminal
(DX+)
Differential input of RS-485
*Note 1
Modbus (RS-485)
communication only uses
pin1, 2.
2
Communication
transmission terminal
(DX-)
3
Power terminal of
KP-605(+16V)
Only for KP-605 linking
4
Auto-detect terminal of
KP-605
Only for KP-605 linking
5
Reserved
Reserved
6
7
Common ports of
KP-605 power(0V)
Only for KP-605 linking
8
Note 1: The
terminal resistor(100Ω) selection is set by DSW1(Default setting: ON)
Note 2: When using multiple sets of drive, connect all the DX
+
, DX
-
terminals of each drive by
series, and connect the shielded net of the connection wire to FG terminal.
Note 3: The function of terminal resistor is to terminate the electric signal and avoid the reflective
signal to interfere the signal. Switch DSW1 to ―ON‖ position of the first and last device
and switch to ―1‖ position for other drives. The default value is ―ON‖ position.
Note 4: The cable length from the controllers(PC, PLC) to the last drive cannot exceed 500m.
Note 5: Max. controller number are 31 sets.