Chapter 5 Parameter Setting Description
101
5
Power
source
Time
Output Freq.
Power failure
re-accelerated
Power
restart
F_051
Start Command Memory
0: Enable (F_001=2,3,4 enable)
1: Disable
5-15 Speed Tracing
F_088
Speed Tracing Current Level
The setting range is 0~200% of drive
rated current.
F_089
Delay Time for Speed Tracing
Set the output delay time before the speed
tracing.
The setting range is 0.1~60.0 sec.
F_090
The V/F Pattern of Speed
Tracing
The setting range is 0~100%
a. When the drive current is greater than the current level of speed tracing (F_088), the output
frequency is tracing downwardly to reach the current level of speed tracing.
b. The speed tracing function is mainly used for tracing the speed for the drive restart after
instantaneous power failure/flying start, the drive fault restart, or the speed tracing command
is given by the input terminal.
c. See the function description of multi-function input terminals for speed tracing on page 85.
5-16 Current Limitation
F_138
Current Limitation
0
:
Disable 1
:
Enable
F_094
Drive Overload(OL1)
0: Disable
1: Thermal protection
2: Current limit overload protection
3: Both 1 and 2 enable