Chapter 5 Parameter Setting Description
76
5
F_003
Selection of ―STOP‖ Key Validity
a. F_003=0
When the start command by terminal, the ―
STOP
RESET
‖ key of keypad disabled.
b. F_003=1
When the start command by terminal, the ―
STOP
RESET
‖ key of keypad enabled.
c. The
applications of “STOP” key.
(I). Emergency stop:
When the start and frequency command are both controlled by multi-function input
terminal (F_001=0 or 1), the output frequency will be decreased to 0Hz and
displaying
on keypad
by pressing ―
STOP
RESET
‖ key during operation.
If the drive needs to be restarted, cut off the wire between the terminals of the start
command (FWD or REV) and COM and restart the drive again.
(II). Normal stop:
F_001=2 or 3, the start command by ―
ON
‖ key of keypad KP-201C and the stop is
controlled by
―
STOP
RESET
‖
key.
F_004
Setting Value (SV) Change Selection
a. F_004=0
In the monitor mode, the setting value cannot be changed by KP-605 keypad to avoid
possible mistakes and errors.
b. F_004=1
In the monitor mode, the setting value can be changed by KP-605 keypad.
F_005
Setting Value (SV) Auto-Storing
a. F_005=0
In the monitor mode, the setting value will not be saved automatically.
b. F_005=1
In the monitor mode, the setting value will be saved automatically after 3 minutes.