Chapter 6 Parameter Description of Pump
110
5
Drive #1
Output
frequency
Actual
pressure
(PV)
Setting
pressure
(SV)
Drive #0
Full
speed
F_022
Drive #0
Drive #1
Time
Time
F_015=2(E-mode)
F_023
Cut-off Frequency of
Parallel Control
․
In multi-pump control systems, set the cut-off
frequency to cut off the pump operation.
F_025
Cut-off Time of
Parallel Control
․
In multi-pump control systems, set the cut-off time to
cut off the pump operation.
1.In multi-pump control systems (E-mode or S-mode), when the output frequency is below the
F_023 and maintaining the time interval (F_025), the drive will depart from the parallel control
system in sequence (Last in - First out).
*Example: Two pumps for parallel control; F_015 = 2 (E-mode).
Output
frequency
Actual
pressure
(PV)
Setting
pressure
(SV)
Drive #0
Drive #1
F_025
F_023
Time
Time
F_015=2(E-mode)
Drive #0
Drive #1