Chapter 6 Parameter Description of Pump
112
6
6-3 Constant Pressure Control Mode and ON / OFF Mode
․
6-3-1 Constant Pressure Control Mode
Func.
Name
Description
F_084
Pressure Boost for
Water Usage Detection
․
Boost the pressure up to detect if the water is used.
F_085
Time Interval of
Pressure Boost for
Water Usage Detection
․
Set the time interval for F_084 to detect if the water
is used.
*0: off
F_086
ON/OFF Mode Starting
Rate Setting
․
In constant pressure control mode and lower water
usage condition, setting the starting rate of drive
switch to ON/OFF mode.
*0: Disable the ON / OFF mode
*The lower setting value means the flow rate
F_115
Acceleration Time of
Pressure Boost
․
Set the time of F_084 (Pressure Boost for Water
Usage Detection) to detect if the water is used.
F_117
Pressure Dead Band
Setting
․
In constant pressure
control mode (F_103≠0), drive
will activate PID control when the feedback signal
exceeds the dead band.
F_133
Drive Stop Frequency
of Water Usage
Detection
․
When the operation frequency is lower than the
setting value, drive will ramp to stop.
1. In constant pressure control mode, drive will auto-detect the water usage according to the
setting of
F_084 (Pressure Boost for Water Usage Detection)
and
F_115 (Acceleration
Time of Pressure Boost)
with the time interval of
F_085 (Time Interval of Pressure Boost
for Water Usage Detection)
to detect the water usage conditions.
Output
Frequency
Actual
Pressure
(PV)
F_084
F_115
F_085
F_085*(100-F_086)%
F_115
F_115
Setting
Pressure
(SV)
F_085
F_115
Water Usage(Large amount condition)
Water Usage
(Little amount
condition)
PID
F_133
F_020 (Primary
deceleration time)
Time
Time
F_117