Chapter 5 Parameter Setting Description
94
5
5-9 Multi-Function Output Setup
F_058
Multi-function Output Terminal (Y1)
F_059
Multi-function Output Terminal (Y2)
F_060
Multi-function Output Terminal (Ta1,Tb1/Tc1)
F_061
Multi-function Output Terminal (Ta2/Tc2)
0: Disable
±1: Running detection
Press
AUTO
ON
, the drive will detect at start
Running detection (F_060=1)
Output
terminal
(Ta1,Tb1)
(SV)
Start
command
Freq.
(PV)
Time
±2: Constant speed detection
Detection at constant speed
±3: Zero speed detection
F_131
Constant speed detection range
0.0~10.0Hz
±4: Frequency detection
F_062
Frequency detection range
0~10Hz
F_063
Frequency detection level
0~120Hz
Output terminal
Time
Output freq.
Freq. detection
range F_062
Freq. detection level F_063
Freq. detection
range F_062
Freq. detection range
(F_059=4)