Chapter 2 Installation and Confirmation
32
2
c. Voltage Selection Board of Cooling Fan
※
RM6F5-4100 above models have the voltage selection board shown in above
figure when removing the main circuit terminal cover of the drive. Please carefully
select the jumper position according to the power source (actual power voltage
level) to avoid the burnout of the fan or the overheating of the drive.
(EX: When the power source is 460V, to select the position from 380V to 460V)
d. Control Terminals
Type
Symbol
Function
Description
C
o
n
tr
o
l
c
ir
c
u
it
t
e
rmi
n
a
l
C
o
n
tr
o
l
p
o
w
e
r
P24
Power terminal;
Control device usage
Output DC+24V; Maximum supplied current
is 50mA.
P12/12V
Output DC+12V; Maximum supplied current
is 20mA.
GND
Common terminal for
analog input control
Grounding terminal for control power
(P12/12V,P24) and analog input terminal
(Vin, Iin).
In
p
u
t
te
rmi
n
a
ls
FWD
Forward command
terminal
Connect the FWD and COM terminals for
forward operation. (F_001=0,1,2)
REV
Reverse command
terminal
Connect the REV and COM terminals for
reverse operation. (F_001=0,1,2)
X1
Multi-function input
terminal 1
․
Connect the X1 and COM terminals and
set the function F_052.
X2
Multi-function input
terminal 2
․
Connect the X2 and COM terminals and
set the function F_053.
X3
Multi-function input
terminal 3
․
Connect the X3 and COM terminals and
set the function F_054.
X4
Multi-function input
terminal 4
․
Connect the X4 and COM terminals and
set the function F_055.
COM
Input common
terminal
The common of input control signal
terminals. (FWD, REV and X1 ~ X4)
Vin
Analog input terminal Input range: DC 0~10V
。