Chapter 4 Parameter List
62
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_083
Time Interval
before
Auto-Restart
Set the error tripping time interval before drive
auto restarts for F_079 when the drive trips to
stop.
1~200 10sec
6
F_084
Pressure Boost
(Water Usage
Detection)
Boost the pressure up to detect if the water is
used.
0.05~1.00
0.01
bar
0.15 112
F_085
Time Interval of
Pressure Boost
(Water Usage
Detection)
Set the time interval for F_084 to detect if the
water is used. (0: off)
0~250
1sec
35
F_086
(ON/OFF
Mode)
Starting Rate
Setting
In constant pressure control mode and under
low flow condition, setting the starting rate of
drive to activate ON/OFF mode. (0: disable)
0~100
1%
0
F_087
(ON/OFF
Mode)
Pressure Dead
Band Setting
In ON/OFF mode, drive will auto start/stop the
pump in accordance with the setting value.
*Start level=SV(Setting pressure) - F_087
Stop level=SV(Setting pressure) + F_087
0.1~25.0 0.1bar 0.3
F_088
Speed Tracing
Current Level
When the current is higher than the ―speed
tracing current level‖, the output frequency
will trace downward.
0~200%
of drive
rated
current
1%
150 101
F_089
Delay Time
before Speed
Tracing
Set the output delay time before the speed
tracing.
0.1~5.0
0.1
sec
0.5
F_090
V/F Curve in
Speed Tracing
Set the percentage of V/F output voltage at
the speed tracing.
0~100%
1%
100 101
F_091 Fault Record Display the latest 5 error records.
─
─
─
F_092
Parameter
Setting Lock
0: Parameters are changeable. Maximum
frequency cannot exceed 120.0Hz.
1: Parameters are locked. Maximum
frequency can not exceed 120.0Hz.
0~3
─
0
F_093
Automatic
Voltage
Regulation
(AVR)
0: Disable
1: Enable
0,1
─
1
F_094
Drive Overload
(OL1)
0: Disable
1: Drive overload
2: Current limit overload protection.
3: Both 1 and 2.
0,1
─
1
F_095 Power Source
The value of setting according to the actual
power source.
190.0~
240.0
0.1V
220.0
(200V
series)
340.0~
480.0
380.0
(400V
series)
F_096
Analog
Frequency
Dead Band
When the signal noise is large, appropriately
increase the dead band to stabilize the
frequency. But this will reduce the tuning
linearity.
0.00~2.55
0.01
Hz
0.00
F_097
Digital Input
Response
Time
When the digital input signal is under the
setting time, program will not be activated.
1~16
1ms
10