Chapter 8 Communication Description
140
8
Convert F_019 to hexadecimal value for generating register number:
18 (decimal) = 12H
Convert 1.5 seconds to hex value: 1.5 x 10 (by resolution) = 15
(decimal) = 000FH
b. Set F_020 (Primary decel time) = 1.5 seconds
Convert F_020 to hex value: 19 (decimal) = 13H
c. Select primary accel/decel time command: register: 2000H, register
data = 00 (b6,b7)
Set the acceleration time F_019 = 1.5 seconds
Address
OP Code
Drive Register
Register Data
MSB
LSB
MSB
LSB
01H
06H
A2H
12H
00H
0FH
Set the deceleration time F_020 = 1.5 seconds
Address
OP Code
Drive Register
Register Data
MSB
LSB
MSB
LSB
01H
06H
A2H
13H
00H
0FH
Select primary acceleration/deceleration time
Address
OP Code
Drive Register
Register Data
MSB
LSB
MSB
LSB
01H
06H
20H
00H
00H
00H
7-9-3 Host Control to Drive
– Read Operation
1. Drive Error Trips (Fault Code):
Example: Drive error trips due to
―GF‖ (grounding fault) and the fault
message displayed at the host.
1) The host sends the below codes to access the drive register
to monitor drive faults (read only one register data)
a.-Drive register: 2100H
b.-Number of register to read: 1
0001H
Message Code (Host to Drive)
Address
OP Code
Drive Register
Register Numbers to
Readout
MSB
LSB
MSB
LSB
01H
03H
21H
00H
00H
01H
2) The drive returns the fault code to the host when
―GF‖ occurs:
-GF code: 0DH
Return Code (Drive to Host)
Address
OP Code
Data Byte
2100H(Register) Data
MSB
LSB
01H
03H
04H
00H
0DH
c. Program the host to convert register data 000DH to
―GF‖
message