Chapter 5 Parameter Setting Description
83
5
F_042
Frequency Upper Limit
Set the ratio of the frequency upper limit (1.00=maximum output frequency), and the
setting range is 0.00~1.00
Output frequency upper limit = Frequency upper limit (F_042) × Maximum output
frequency (F_017)
F_043
Frequency Lower Limit
Set the ratio of the frequency lower limit (1.00=maximum output frequency), and the
setting range is 0.00~1.00
Output frequency lower limit = Frequency lower limit (F_043) × Maximum output
frequency (F0_17)
Output
frequency
Frequency
command
60.0Hz
60.0Hz
54.0Hz
54.0Hz
6.0Hz
6.0Hz
Max. output freq.60.0Hz
Freq. upper limit=0.90
Freq. lower limit=0.10