Chapter 4 Parameter List
57
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_017
Maximum
Output
Frequency
The maximum output frequency of drive.
0.1~120.0 0.1Hz 60.0
F_018
Reference
Frequency of
Accel/Decel
Time
The frequency corresponding to
accel/decel time.
0.01~
400.00
0.01
Hz
60.00
F_019
Primary
Acceleration
Time
The acceleration time from stop to
reference frequency.
0.0~
3200.0
0.1
sec
1.0
(note3)
F_020
Primary
Deceleration
Time
The deceleration time from reference
frequency to stop.
0.0~
3200.0
0.1
sec
1.0
(note3)
F_021
Launch
Detection Time
(Parallel
Control)
In multi-pump control systems,
If the pressure decreasing gradually, set
the detection time to launch auxiliary drive.
0.0~25.0
0.1
sec
6.0
F_022
Launch
Detection Level
(Parallel
Control)
In multi-pump control systems, set the
detection level when the pressure
decreasing gradually.
0.2~25.0 0.1bar 0.4
F_023
Cut-off
Frequency
(Parallel
Control)
In multi-pump control systems,set the
cut-off frequency and start frequency for
lead/auxiliary drive stopping.
0.0~60.0 0.1Hz 50.0
F_024
Pump
Auto Shift Time
(Parallel
Control)
The time of pump shift operation in
multi-pumps control system.
0~240
1 hr
24
F_025
Cut-off Time
(Parallel
Control)
In multi-pump control systems, the
detection time of pump departs from
operation.
0.0~25.0
0.1
sec
10.0
F_026
Communi-
cation Baud
Rate
(Parallel
Control)
The communication baud rate setting for
multi-pump control systems.
0~3
─
1
─
F_027
Secondary
Acceleration
Time
Multi-function input terminals select the
secondary acceleration time.
0.0~
3200.0
0.1
sec
0.5
F_028
Secondary
Deceleration
Time
Multi-function input terminals select the
secondary deceleration time.
0.0~
3200.0
0.1
sec
0.5
F_029
Set S-curve for
Accel/Decel
Time
Set S-curve to slow the acceleration and
deceleration time at start and stop.
0.0~5.0
0.1
sec
0.0
F_030
V/F Pattern
Selection
0: Linear
1: Square curve.
2: 1.7
th
power curve.
3: 1.5
th
power curve.
0~3
─
1
The color as means the function can be set during the operation.
Summary of Contents for RM6F5 series
Page 1: ...AC MOTOR DRIVE Operation Manual RM6F5 series ...
Page 194: ...Notes 194 Notes ...
Page 195: ...Notes 195 Notes ...