Chapter 5 Parameter Setting Description
87
5
5-6 Analog Output Setup
The analog output terminals:
―FM+‖ – ―M-‖: DC 0 ~ 10V;
―AM+‖ – ―M-‖: DC 0 ~ 10V
(1/2 HP ~ 5HP models are marked by ―FM+‖ – ―GND‖ and ―AM+‖ – ―GND‖)
F_044
Analog Output Signal Selection(FM+)
F_129
Analog Output Signal Selection(AM+)
0: Output frequency
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the output
frequency. (the terminal will output signal when drive operation)
1: Frequency command
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the
frequency command. (the terminal will output when drive is operation or stop)
2: Output current
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the output
current. (max. corresponding value is rated output current of drive)
3: “Vin” analog input signal
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the signal
of ―Vin‖ analong input terminal. (the setting is activation when F_124=1)
4: “Iin” analog input signal
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the signal
of ―Iin‖ analong input terminal. (the setting is activation when F_125=1)