Chapter 4 Parameter List
63
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_098
Grounding
Fault
Protection (GF)
0: Disable
1: Enable(GF)
0, 1
─
1
F_099
External
Indicator 1
Select the monitor mode of external indicator 1
0: Disable
0~8
─
1
F_100
External
Indicator 2
Select the monitor mode of external indicator 2
0: Disable
0~8
─
5
F_101
External
Indicator 3
Select the monitor mode of external indicator 3
0: Disable
0~8
─
2
F_102
PID
Compensa-
tion Gain
Compensate the gain for pressure command
control under constant pressure control.
0.1~8.0
─
1.0
F_103
PID Control
Mode
Selection
0: Open-loop operation
1: Forward control; D postposition
2: Forward control; D preposition
3: Reverse control; D postposition
4: Reverse control; D preposition
0~4
─
1
F_104
P Selection
0: P postposition
1: P preposition
0,1
─
1
F_105
Proportional
Gain(P)
Set the gain value for deviation adjustment.
(0.0: P control disabled)
0.0~25.0
0.1
3.0
F_106
Integration
Time(I)
Set the integration time for deviation
adjustment. (0.0: I control disabled)
0.0~25.0
0.1
sec
1.2
F_107
Derivative
Time(D)
Set the derivative time for deviation
adjustment. (0.00: D control disabled)
0.00~2.50
0.01
sec
0.00 114
F_108
Derivative
Time of
Feedback
Set the derivative time for feedback signal.
0.00~2.50
0.01
sec
0.00 114
F_109
Integration
Upper
Limitation
Set the upper limitation value of integrator.
0~200%
of maximum
frequency
1%
100
─
F_110
Integration
Lower
Limitation
Set the lower limitation value of integrator.
-100~100%
of maximum
frequency
1%
0
─
F_111
Offset
Adjustment for
Integration
Time
Adjust the integration time offset.
-100~100%
of maximum
frequency
1%
65
F_112
PID Buffer
Space
Set the buffer space of PID output value.
0~255
─
2
─
F_113
Feedback
Signal Filter
Filter the feedback signal.
0~255
─
10
─
F_114
Feedback
Signal Trip
Detection
0: Disable
1: Enable (at F_126=0)
0,1
─
1
F_115
(Water Usage)
Pressure Boost
Time
Set the time of F_084 (Pressure Boost for
Water Usage Detection) to detect if the water
is used.
0.1~25.0
─
0.6
F_116
Parameter
Selection
0: F_000 ~ F_134
1: F_000 ~ F_194
0,1
─
0
─
The color as means the function can be set during the operation.