Chapter 4 Parameter List
67
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_157
Communica-
tion Protocol
0: 8,N,2
1: 8,E,1
2: 8,O,1
0~2
─
1
F_158
Communica-
tion Overtime
(Cot)
When the data transmission during
communication transmission is interrupted,
has no data transmitting, or delays, drive
displays ―Cot‖ message
(0.0: Communication overtime disable)
0~1000
1sec
0.0
F_159
Communica-
tion
Overtime
Disposal
0: Warning (Cot): Continue
operation.
1: Warning (Cot): Ramp to stop
2: Warning (Cot): Coast to stop
0~2
─
0
F_160
Multi-Function
Input Selection
0: Multi-function inputs from
multi-function terminals
1: Multi-function inputs from
communication control
0,1
─
0
F_162
Frequency
Upper
Limitation by
Manual Mode
Setting manual mode for upper limit of
frequency command
0~100%
maximum
of output
frequency
1%
100
F_163
Frequency
Lower
Limitation by
Manual Mode
Setting manual mode for lower limit of
frequency command
0~100%
maximum
of output
frequency
1%
0
F_166
K Value of
Flow Sensor
Setting value accord with specification of flow
sensor
0.1~100.0
1L
/Pulse
10.0
F_167
Rate of Flow
Sensor
Setting rate of flow sensor
0.00~2.00 0.01 1.00
F_168
Unit of Flow
Sensor
0: LPS
1: CMH
0,1
─
0
F_171
Shutoff
Head(H)
Setting shutoff head of pump
0~160
0.1bar 12.0
F_172
Maximum
Flow (Q)
Setting maximum flow of pump
0.0~
6000.0
0.1L/
min
300.0 124
F_173
Compensa-
tion for Pipe
Friction Loss
0:Disable
1:Enable
0,1
─
0
F_174
The Current in
Maximum
Flow
(I
Qmax
)
Setting current in maximum flow(I
Qmax
)
1~200% of
drive rated
current
1%
100
F_175
The Current in
Minimum Flow
(I
Qmin
)
Setting current in minimum flow(I
Qmin
)
0~200% of
drive rated
current
1%
30
The color as means the function can be set during the operation.