Chapter 5 Parameter Setting Description
75
5
F_002
Frequency Command Selection
a. F_002=0
Frequency command by “Vin” or “Iin” analog input terminal (select Vin or Iin
analog input sources by F_123).
(I). Vin-GND: Input range DC 0~10V
。
※
The gain or bias of frequency command can be set by function F_040 and F_041.
(II). Iin-GND: Selec
t the input signal mode via ―JP4‖ switch.
JP4
I position (current signal); Range: 4~20mA or 0~20mA (set by F_126).
JP4
V position (voltage signal); Range: 2~10V or 0~10V (set by F_126).
※
The gain or bias of frequency command can be set by function F_127 and F_128.
b. F_002=1
Frequency command by keypad.
(I). In keypad KP-605, the primary speed, jog speed and preset speeds (F_009 ~
F_017) can be set during operation and the frequency command can be set
under monitor mode.
(II). In keypad KP-605, the pot knob can be defined by speed control.
c. F_002=2
Pressure command by keypad (KP-605).
d. F_002=3
Frequency command by
RS-485.
Related control command refer to
―6-6 Drive Registors and Command Code‖
e. F_002=4
Pressure command by RS-485.
Related control command refer to ―6-6 Drive Registors and Command Code‖
※
Note: In monitor mode, when F_002 sets 1, 2 or 3, pressing
▲
or
▼
key one time
and the frequency command will be blink but not changing. Press the
▲
or
▼
key
again to change the frequency command.
Summary of Contents for RM6F5 series
Page 1: ...AC MOTOR DRIVE Operation Manual RM6F5 series ...
Page 194: ...Notes 194 Notes ...