Chapter 2 Installation and Confirmation
40
2
2-4 Wiring Diagram and Setting for Single-pump and Multi-pump Applications
2-4-1 Single Pump Control
Drive #0
I
V
Pressure
transducer
JP4
ON
DSW3
1
P24 Iin DX+ DX- FG
JP1
–
+
Drive #0
Setting
Description
Content
Func.
F_015
(Selection of Parallel Control
Mode)
=1(Single pump)
F_016
(
Set Drive’s No. in Parallel
Control)
=0(Drive#0)
JP1/JP4
Selection
JP1
Impedance selection of Iin
(Open
﹕
500Ω
;
Close
﹕
250Ω)
Open
JP4
Input signal type selection of Iin
(Voltage/Current)
I position
Terminal Resistor
Switch
DSW3
ON position