Chapter 5 Parameter Setting Description
98
5
5-11
System Overload Detection SetUp
F_065
System Overload Detection(OLO)
a. The settings are listed as below:
0: Disable
1: Enable (OLO)
F_066
System Overload Detection Status
0: Detection at constant speed only.
1: Detection at operation: Including the system overload at acceleration, deceleration or
constant speed.
F_067
Output Setting of System Overload
0: Drive continues running after the system overload is detected
1: Drive trips after the system overload is detected.
F_068
System Overload Detection Level
Setting the level of current for system overload detection, and the setting range is 30~200% of
drive rated current.
F_069
System Overload Detection Time
a. The detection of system overload is shown in the below chart:
Overload
detection
Overload
detection level
F_068
Current
Time
Time
Overload detection time
F_069
Time interval<overload detection time
b. The operation panel displays ―OLO‖, when the system overload time is over the setting value
of system overload detection time (F_069).
c. Setting range: 0.1~25.