Chapter 2 Installation and Confirmation
33
2
Type
Symbol
Function
Description
Iin
Analog input terminal
․
Input signal selection
JP4: I position (current signal)
JP4: V position (voltage signal)
․
Input range: DC 4~20mA (2~10V) or
DC 0~20mA (0~10V)
․
The function is set by F_126.
C
o
n
tr
o
l
c
ir
c
u
it
t
e
rmi
n
a
l
Ou
tp
u
t
te
rmi
n
a
ls
FM+
AM+
Analog output
terminal
․
Voltage meter with 10V full scale spec.
(meter impedance: 10K
Ω above)
․
Maximum output current: 1mA
M-
(GND)
Common of analog
output terminals
Common of analog output terminals.
Ta1
Multi-function output
terminals
(relay type)
․
N.O (form a contact); The function is set
by F_060
․
Capacity: AC250V, 0.5AMax, cos
θ=0.3
Tb1
․
N.C (form b contact); The function is set
by F_060
․
Capacity: AC250V, 0.5AMax, cos
θ=0.3
Tc1
Common terminal for Ta1,Tb1.
Ta2
․
N.O (form a contact); The function is set
by F_061.
․
Capacity: AC250V, 0.5AMax, cos
θ=0.3
Tc2
Common terminal for Ta2.
Y1
Multi-function output
terminals
(open collector type)
․
The function is set by F_058
,
F_059.
․
Capacity: DC48V, 50mAMax
Y2
CME
Common terminal of Y1, Y2.
FG(A8)
Connect the shielded net to FG(A8) and
avoid
the reflective signal to interfere the signal.
FM_P
Reserved
e. Control Terminals and Switch for Communication Application
Type
Symbol
Function
Description
C
o
mm
u
n
ic
a
tion
te
rmi
n
a
ls
DX+
Multiple pump/
Modbus
communication
terminal
․
Connect the RM6F5 series drives by
transmission cable, when the drives
control multiple pumps.
․
Maximum parallel units:2 units
DX-
FG
Grounding terminal
of signal
transmission
Grounding terminal of shielding wire.
T
e
rmi
n
a
l
re
s
is
to
r
DSW3
Terminal resistor
switch
․
Switch the DSW3 to
―ON‖ position for first
and last drives, when parallel control the
multi-pump system.
․
Terminal resistance:
100Ω
Note: The total length of connecting cable can not exceed 500 meters.