Chapter 2 Installation and Confirmation
35
2
2-3-5 Control Board
(1) RM6F5-2001 ~ RM6F5-2005;
RM6F5-4001 ~ RM6F5-4007
Tb1
Y2
CME
FWD
Y1
COM
REV
24V
X4
SOURCE
3
2
1
COM
X3
X2
X1 FM_P
JP5
SINK
SINK
SOURCE
JP5
SOURCE
TB1
SOURCE
SINK
SINK
TB3
12V
AM+
FM+
CN1
5
M-
GND
Vin
Iin
V
I
DX+
DX-
FG
Tc1
Ta1
1
JP4
JP1
JP4
I mode
V mode
DSW3
1
ON
CN3
GFD
TB2
Ta2
Tc2
CN1: External indicator (DM-501) socket.
CN3: Digital keypad (KP-605) RJ-45 socket / RS-485 communication interface
(choose one of the two options)
TB1: Input/Output terminals.
TB2: Multi-function output terminals (relay type).
TB3: Connection terminals for multi-pump control/RS-485 communication
interface. (choose one of the two options)
JP1: Input impedance selection of Iin (close:
250Ω ; open: 500Ω); Default: close.
JP4: Input signal type selection of Iin (voltage/current). Default: current
JP5: SINK/SOURCE mode selection of X1 to X4, FWD or REV (refer to page 18).
Default: SINK
DSW3: Terminal resistor switch (ON: enable; 1: disable).