Chapter 4 Parameter List
60
4
Func.
Name
Description
Range
of
Setting
Unit Def50 Page
F_058
Multi-function
Output
Terminal (Y1)
0: Disable
±1: Standby detection
±2: Constant speed detection.
±3: Zero speed detection.
±4: Frequency detection.
±5: System overload detection. (OLO)
±6: Stall prevention detection.
±7: Low voltage detection. (LE)
±8: Braking detection.
±9: Restart after instantaneous power
failure detection.
±10: Restart after error condition detection
±11: Error detection.
±12: Overheating warning detection. (Ht)
±13: Over pressure detection. (OP)
±15: Auxiliary pump 1 detection.
±16: Auxiliary pump 2 detection.
±17: Fan detection during operation.
-17~ +17
(Note 5)
─
1
F_059
Multi-function
Output
Terminal (Y2)
2
F_060
Multi-function
Output
Terminal
(Ta1,Tb1)
-11
F_061
Multi-function
Output
Terminal
(Ta2/Tc2)
-3
F_062
Frequency
Detection
Range
Set the bandwidth of frequency detection
range.
0.0~
10.0
0.1Hz
2.0
F_063
Frequency
Detection
Level
Set the frequency detection level of
multi-function output terminal.
0.0~
400.0
0.1Hz
0.0
F_064
Automatic
Boost Voltage
Range
According to the load condition, adjust the
output voltage of the V/F Pattern. (0.0: Off)
0.0~
25.5
0.1
1.0
F_065
System
Overload
Detection
(OLO)
0: Disable
1: Enable(OLO)
0,1
─
0
F_066
System
Overload
Detecting
Selection
0: Detection during constant speed only
1: Detection during operation only
0,1
─
0
F_067
Output Setting
after System
Overload
0: Drive keeps operation when the
overload is detected
1: Drive trips to protection when the
overload is detected
0,1
─
0
F_068
System
Overload
Detection
Level
The output current is larger than the level
and exceeds the time interval(F_069) of
the overload detection.
30%~
200%
of drive
rated
current
1%
160
F_069
System
Overload
Detection Time
The output current is larger than the level
(F_068) and exceeds the time interval of
the overload detection.
0.1~
25.0
0.1
sec
F_070
Stall
Prevention
Level at
Acceleration
If stall is occurred during acceleration, the
motor keeps running at the constant speed.
30%~
200%
of drive
rated
current
1%
140