Chapter 5 Parameter Setting Description
92
5
±11: Speed tracing from the setting frequency
Speed tracing from the setting frequency
(F_053=11)
Terminal start
command (FWD)
Decel. time is 2 sec
Delay Time
before Speed
Tracing(F_089)
The current level of
speed tracing (F_088)
Normal accel. time
> 0.1sec
Speed tracing
command
(X1)
Setting frequency
Output frequency
Output voltage
Output current
The V/F Pattern of
Speed Tracing(F_090)
Return to normal V/F
The current level of
speed tracing
±12: Accel/Decel disable (Please refer to page 74)
±13: In closed-loop control
(F_103 ≠ 0), opened-loop selection.
*
In closed-loop control, temporarily run bypass signa ,controlled by analog input
signal (Vin or Iin) or frequency command of preset speed.
±14: In closed-loop control
(F_103 ≠ 0), integrator reset.
±15: Stop command
*After the terminal is acted, the drive will decelerate and stop.
±16: Analog input source selection
Select Vin or Iin to as the analog input signal.
F_123 = 3 (Vin or Iin)
+16
Terminals short circuited: Vin Analog Input Source
Terminals open circuited: Iin Analog Input Source
-16
Terminals short circuited:
Iin Analog Input Source
Terminals open circuited: Vin Analog Input Source
±17: Auxiliary pump start command 1
±18: Auxiliary pump start command 2
*Auxiliary pump 1, 2 start command, only suitable for S-mode.
*Please refer to ―2-4-4 multi-pump control (S-mode)‖
。
±19: Auxiliary pump error command ( P1_OL)
±20: Auxiliary pump error command ( P2_OL)
*In S-mode control, auxiliary pump 1, 2 error signal command.
If the error state was removed, the drive will return to normal status.
*Please refer to ―2-4-4 multi-pump control (S-mode)‖ on page36.