Chapter 2 Installation and Confirmation
15
2
Model name
(RM6F5-
□□□□
)
4150 4175 4200 4250 4300 4350 4420 4500 4600 4700
Maximum applicable
motor (HP / kW)
150/
110
175/
132
200/
160
250/
200
300/
220
350/
250
420/
315
500/
375
600/
450
700/
500
Rated output capability
(kVA)
160 193 232 287 316 366 396 533 655 732
Rated output current
(A)
210 253 304 377 415 480 520 700 860 960
Rated output voltage
(V)
Three-phase 380~480V
Range of output
frequency (Hz)
0.1~120.00Hz
Power source (
ψ
, V,
Hz)
Three-phase 380~480V 50/60Hz
Input current (A)
196 217 282 355 385 440 540 650 800 900
Permissible AC power
source fluctuation
332~528V 50/60Hz / ±5
%
Overload protection
120% of drive rated output current for 1 min.
Cooling method
Fan cooling
Applicable safety
standards
-
Protective structure
IP00 (IP20 OPTION)
IP00
Weight / Mass(kg)
47
65
91
95
97
159 163 217 217 272
※
The weight illustrated in the standard specifications of RM6F5 series does not include the
weights of AC reactor(ACL) and DC reactor(DCL).
Summary of Contents for RM6F5 series
Page 1: ...AC MOTOR DRIVE Operation Manual RM6F5 series ...
Page 194: ...Notes 194 Notes ...
Page 195: ...Notes 195 Notes ...