Chapter 2 Installation and Confirmation
43
2
Wiring 3 ( Special wiring )
Drive #0
-
+
Drive #1
Drive #2
ON
I
V
I
V
I
V
Pressure
transducer
Drive#3
I
V
DSW3
JP4
JP4
JP4
JP4
1
ON
DSW3
1
ON
DSW3
1
ON
DSW3
1
P24 Iin DX+ DX- FG
P24 Iin DX+ DX- FG
P24 Iin DX+ DX- FG
P24 Iin DX+ DX- FG
JP1
JP1
JP1
JP1
※
( Dotted line: more than three pumps according customer requirement to set up )
Drive #0
Setting
Description
Content
Func.
F_015
(Selection of Parallel Control
Mode)
=2 (E-mode) or
=3 (F-mode) or
=4 (M-mode)
F_016
(
Set Drive’s No. for Parallel
Control)
=0(Drive#0)
JP1/JP4
Selection
JP1
Impedence selection of Iin
(Open
﹕
500Ω
;
Close
﹕
250Ω)
Open
JP4
Input signal type selection of Iin
(Voltage/Current)
I position
Terminal Resistor
Switch
DSW3
ON position
Auxiliary Drive #1 (#2,#3)
Setting
Description
Content
Func.
F_015
(Selection of Parallel Control
Mode)
=2 (E-mode) or
=3 (F-mode) or
=4 (M-mode)
F_016
(
Set Drive’s No. for Parallel
Cntrol)
=1
JP1/JP4
Selection
JP1
Impedence selection of Iin
(Open
﹕
500Ω
;
Close
﹕
250Ω)
Close
JP4
Input signal type selection of Iin
(Voltage/Current)
V position
Terminal Resistor
Switch
DSW3
#1, #2: 1 position
#3:
ON position
※
Note: Dual drive (or multi-drive) independently use a set of pressure sensor and parallel
pressure signal. If the drive(#0) error occurs, auxiliary drive (#1,#2,#3) will control pressure
signal.