Chapter 5 Parameter Setting Description
82
5
5-4 V/F Pattern Setup
F_009
Starting Frequency
Range: 0.1~10.0Hz
F_010
Starting Voltage
The range of 200V series is 0.1 ~ 50.0V.
The range of 400V series is 0.1 ~ 100.0V.
F_011
Base Frequency
Motor base frequency;
The setting must be according to the nameplate of motor.
F_012
Base Voltage
Motor base voltage;
The setting must be according to the nameplate of motor.
(200V series: 0.1~255.0V; 400V series: 0.1~510.0V)
F_017
Maximum Output Frequency
RM5P series: The setting range of max output frequency is 0.1 ~ 120.0.
F_030
V/F Pattern Selection
a. The settings are listed as below:
0: Linear
1: Energy saving mode (Auto-adjust V/F according to the loads)
2: Square curve
3: 1.7
th
power curve
Base freq.
Output
voltage
Output freq.
70%
100%
Below 50% of drive
rated current
Linear
Energy saving
Square of 2 curve
Square of 1.7 curve
Square of 1.5 curve