5-27-6 SELECT EM BANK: EMBC(171)
(171)
EMBC
N
N: EM bank number
CIO, G, A, #, DM, DR, IR
Operand Data Area
Ladder Symbol
Variations
j
EMBC(171)
When the execution condition is OFF, EMBC(171) is not executed. When the
execution condition is ON, EMBC(171) changes the current EM bank to the one
indicated by the EM bank number (N).
The current EM bank number is recorded in the least significant (rightmost) digit
of A511. Bit A51115 is ON when EM is mounted to the CPU.
N must be between 0000 and 0007.
EMBC(171) can be used only with CPUs that support the EM Area.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
N is not between 0000 and 0007.
The EM Unit does not have the EM bank indicated by N, or
the indicated bank is being used as file memory.
Content of
*
DM word is not BCD when set for BCD.
Description
Precautions
Special Instructions
Section 5-27