BAND 0001 D00100 D00110
0000
00
328
Precautions
The lower limit (C) must be less than or equal to the upper limit (C+1).
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
The upper limit setting is less than the lower limit.
The content of a
*
DM word is not BCD when set for BCD.
> (A50005):
The input data (S) is greater than the upper limit (C+1).
EQ (A50006):
The output data is all zeros.
< (A50007):
The input data (S) is less than the lower limit (C).
N (A50008):
The output data is a negative number.
Example
When CIO 000000 turns ON in the following example, one of the following will
occur:
•
If the binary content of CIO 0001 is within the range specified by the content of
D00100 and D00101, 0000 will be output to D00110.
•
If the binary content of CIO 0001 is greater than the content of D00101, the
result of (CIO 0001 minus D00101) will be output to D00110.
•
If the binary content of CIO 0001 is less than the content of D00100, the result
of (CIO 0001 minus D00100) will be output to D00110.
Address
Instruction
Operands
00000
LD
000000
00001
BAND(272)
0001
D00100
D00110
4FFF
CIO 0001
41F5
D00110
0000
1000
1000 < 41F5 < 4FFF
E325
A50006 (=) ON
D00101 D00100
0000
4FFF
CIO 0001
D00110
28CD
78CC < 4FFF
A50005 (>) ON
D00101 D00100
78CC
78CC – 4FFF = 28CD
5-24-4 DEAD-ZONE CONTROL: ZONE(273)
(273)
ZONE
S
C
D
Ladder Symbol
Variations
↑
ZONE(273)
Operand Data Areas
D: Output word
CIO, G, A, T, C, DM, DR, IR
C: First bias word
CIO, G, A, T, C, DM
S: Input word
CIO, G, A, T, C, #, DM, DR, IR
Description
When the execution condition is OFF, ZONE(273) is not executed. When the ex-
ecution condition is ON, ZONE(273) adds the specified bias to the specified in-
put data (signed 16-bit binary) and places the result in a specified word. The con-
tents of words C and C+1 are as follows:
C
Negative bias
C+1
Positive bias
If the input data (S) is less than zero, the input data plus the negative bias will be
output to D and the Less Than Flag (A50007) will turn ON.