172
5-14-22 DOUBLE ROTATE RIGHT W/O CARRY: RRNL(263)
(263)
RRNL Wd
Wd: Word
CIO, G, A, DM
Operand Data Area
Ladder Symbol
Variations
↑
RRNL(263)
When the execution condition is OFF, RRNL(263) is not executed. When the ex-
ecution condition is ON, RRNL(263) shifts all bits previously in Wd and Wd+1 to
the right, and bit 00 of Wd is shifted into both bit 15 of Wd+1 and into CY.
Wd+1
Wd
CY
Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
CY (A50004):
Receives the status of bit 00 from Wd.
EQ (A50006):
Content of Wd and Wd+1 are 0 after execution.
N (A50008):
Same status as bit 15 of Wd+1 after execution.
Example
When CIO 000000 is ON in the following example, the status of bit 00 of
CIO 0800 is shifted into bit 15 of CIO 0801 and into CY, the status of all bits within
CIO 0801 are shifted right one position, the status of bit 00 is shifted to bit 15 of
CIO 0800, and the status of all bits within CIO 0800 are shifted left one position.
Address
Instruction
Operands
00000
LD
000000
00001
RRNL(263)
0100
1 0 0 1
0 1 1 0
0
CY
LSB
MSB
1 0 0
0 0 1 1
1
CY
LSB
MSB
1 0 1 1
0 0 1
0 1 0 1
1 1 0 1
LSB
MSB
LSB
MSB
Wd+1: CIO 0801
Wd: CIO 0800
Wd+1: CIO 0801
Wd: CIO 0800
1
Description
Precautions
Shift Instructions
Section 5-14
0000
00
(263)