109
5-6-2 CONDITION ON/OFF: UP(018) and DOWN(019)
DOWN
Ladder Symbols
(018)
UP
(019)
Description
UP(018) turns ON the execution condition for one cycle at the rising edge (OFF
to ON) of the execution condition and then turns OFF the execution condition
until the next time a rising edge is detected.
DOWN(019) turns ON the execution condition for one cycle at the falling edge
(ON to OFF) of the execution condition and then turns OFF the execution condi-
tion until the next time a falling edge is detected.
Another instruction must follow UP(018) or DOWN(019), i.e., they cannot be
used as right-hand instructions.
Precautions
Be careful when using UP(018) and DOWN(019) in subroutines between IL and
ILC, and between JMP and JME instructions, because the execution condition
may remain ON for more than one scan. Refer to 5-8 INTERLOCK and INTER-
LOCK CLEAR: IL(002) and ILC(003), 5-9 JUMP and JUMP END: JMP(004) and
JME(005), and 5-30 Subroutines for details.
The DIFU(013) and DIFD(014) instructions can also be used for the same pur-
pose, but they require work bits. UP(018) and DOWN(019) simplify program-
ming by reducing the number of work bits and program addresses needed.
Flags
There are no flags affected by UP(018) or DOWN(019).
Example
The timing chart illustrates the operation of UP(018) and DOWN(019) in the fol-
lowing example.
(018)
UP
0000
01
0000
02
0001
01
0001
02
(019)
DOWN
00001
LD
000001
00002
OR
000002
00003
OUT
TR0
00004
UP(018)
00005
OUT
00101
00006
LD
TR0
00007
DOWN(019)
00008
OUT
000102
Address Instruction
Operands
Input CIO 000001
Input CIO 000002
Output CIO 000101
Output CIO 000102
t: Cycle time
TR0
Ladder Diagram Instructions
Section 5-6