![Omron CVM1D Operation Manual Download Page 356](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532356.webp)
(189)
IODP
D15000
0200
0000
00
351
Bits 00 to 06 specify the Unit to which the characters will be output (specifics are
shown in the following diagram). Bit 07 determines whether the source data is
hexadecimal (OFF) or 7-segment display code (ON). Bit 08 determines whether
the characters will flash (ON) or not (OFF).
If bit 09 of C is set for automatic display (ON), the characters will be displayed
regardless of the Unit’s display mode, but if bit 09 of C is OFF, the characters will
be displayed only when the Unit is set to display mode 3.
15
10 09 08 07 06 05 04 03
00
Unit type
0 (OFF): I/O Control/Interface
1 (ON):
Remote I/O Slave
Rack number/
Slave number
Not used,
set to zero.
Data type
0 (OFF): Hexadecimal
1 (ON):
7-segment display code
C:
Automatic display
0 (OFF): No
1 (ON):
Yes
Flashing display
0 (OFF): No
1 (ON):
Yes
Master address
(Set to zero if
bit 06 is zero.)
If bit 07 is set for hexadecimal data, the characters are output as they are in the
source word. The rightmost digit will be the rightmost on the display.
If bit 07 is set for 7-segment display code, segments a to f of the leftmost digit are
contained in S bits 00 to 06, segments a to f of the second digit are contained in S
bits 08 to 14. Set bits 07 and 15 to zero. The segments for the third and fourth
digits follow the same pattern in word S+1, as shown in the following diagram.
The table shows the number of the bit that must be turned ON in S or S+1 to turn
ON each segment of each digit in the display.
Segment
g
f
e
d
c
b
a
S
Digit 1
06
05
04
03
02
01
00
Digit 2
14
13
12
11
10
09
08
S+1
Digit 3
06
05
04
03
02
01
00
Digit 4
14
13
12
11
10
09
08
S cannot be the last word in a data area when S and S+1 contain 7-segment
display code.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
Control word data is incorrect.
The following example show how to produce the display “
a051
” from both a
7-segment display code.
When CIO 000000 is ON, the content of CIO 0200 and CIO 0201 is displayed
according to the specifications in D15000.
Address
Instruction
Operands
00000
LD
000000
00001
IODP(189)
D15000
0200
Precautions
Example
Special Instructions
Section 5-27
g
f
b
c
d
e
a
Summary of Contents for CVM1D
Page 462: ...SYSMAC CVM1D Duplex System Programmable Controllers Operation Manual Revised August 2001...
Page 463: ...iv...
Page 465: ...vi...