![background image](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532134.webp)
129
The first MOV(030) instruction moves the PC memory address of the PV for tim-
er T0000 ($1000) to IR0. The first MOVR(036) instruction moves the PC
memory address of the Completion Flag for timer T0000 to IR1, and the second
one moves the starting address into IR2. The second MOV(030) instruction
moves the address (00100) of the DM word that contains the SV for timer T0000
to D00000. A50013 is an Always ON Flag.
JME(005) and JMP(004) form a loop in which the content of IR0, IR1, and
D00000 are incremented by one each time the program executes the loop,
successively defining and starting the 100 timers T0000 through T0199. The
loop continues until the content of D00000 is 0200, i.e., until all 100 timers have
been defined and started. A50006 is the Equals Flag.
The subroutine above is equivalent to the 400 instructions below.
00000
LD NOT
200000
00001
TIM
0000
D00100
00002
LD
T0000
00003
OUT
200000
00004
LD NOT
200001
00005
TIM
0001
D00101
00006
LD
T0001
00007
OUT
200001
00008
LD NOT
200002
00009
TIM
0002
D00102
00010
LD
T0002
00011
OUT
200002
00396
LD NOT
200602
00397
TIM
0099
D00199
00398
LD
T0000
00399
OUT
200602
Instruction
Address
Operands
2000
2000
2000
2006
TIM
0000 D00100
TIM
0001 D00101
TIM
0002 D00102
TIM
0099 D00199
2000
T0000
00
2000
T0001
01
2000
T0000
02
2006
T0099
02
00
01
02
02
5-13-1 TIMER: TIM
TIM
N
S
S: Set value
CIO, G, A, T, C, #, DM, DR, IR
*Refer to page 128 for details on indirectly addressing timers.
N: Timer number
#
Operand Data Areas
Ladder Symbol
Description
A timer is activated when its execution condition goes ON and is reset (to SV)
when the execution condition goes OFF. Once activated, TIM measures in units
of 0.1 second from the SV.
If the execution condition remains ON long enough for TIM to time down to zero,
the Completion Flag for the timer number used will turn ON and will remain ON
until TIM is reset (i.e., until its execution condition goes OFF or CNR(236) is
executed).
Timer and Counter Instructions