![Omron CVM1D Operation Manual Download Page 158](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532158.webp)
153
5-14-4 WORD SHIFT: WSFT(053)
Variations
j
WSFT(053)
(053)
WSFT
S
St
E
Operand Data Areas
Ladder Symbol
S: Source word
CIO, G, A, T, C, #, DM, DR, IR
E: End word
CIO, G, A, DM
St: Starting word
CIO, G, A, DM
When the execution condition is OFF, WSFT(053) is not executed. When the ex-
ecution condition is ON, WSFT(053) shifts data between St and E in word units.
The data in S is copied into St and the content of E is lost.
F
0
C
2
3
4
5
2
1
0
2
9
E
St + 1
St
3
4
5
2
1
0
2
9
4
B
C
0
E
St + 1
St
Lost
4
B
C
0
S
St must be less than or equal to E. St and E must be in the same data area.
The shift operation might not be completed if a power interruption occurs during
execution of the instruction.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
The St and E words are in different areas, or St is greater
than E.
Example
When CIO 000000 is ON in the following example, FF00 is shifted into D00010,
the word data in D00010 is shifted to D00011, the word data in D00011 is shifted
to D00012, and the word data in D00012 is lost.
Address
Instruction
Operands
00000
LD
000000
00001
WSFT(053)
#FF00
D00010
D00012
Lost data
St+1: D00011
5 6 7 8
E: D00012
5 6 7 8
St+1: D00011
9 A B C
9 A B C
St: D00010
F F 0 0
S : #FF00
E: D00012
1 2 3 4
St: D00010
Description
Precautions
Shift Instructions
Section 5-14
(053)
WSFT
#FF00
D00010
D00012
0000
00