0000
00
(236)
CNR
T0001
T0005
146
Precautions
D
1
and D
2
must be in the same data area, and D
1
must be less than or equal to
D
2
. If D
1
w
D
2
, only D
1
will be reset.
Note: Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
Example
The CNR(236) instruction in the example below resets timers T0001 to T0005 to
their SV whenever CIO 000000 turns ON.
Address
Instruction
Operands
00000
LD
000000
00001
CNR(236)
T0001
T0005
Timer and Counter Instructions
Section 5-13