![Omron CVM1D Operation Manual Download Page 120](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532120.webp)
115
5-7-3 SET and RESET: SET(016) and RSET(017)
SET: SET(016)
(016)
SET
B
B: Bit
CIO, G, A
Operand Data Area
Ladder Symbol
Variations
j
SET(016)
!
j
SET(016)
i
SET(016)
!
i
SET(016)
!SET(016)
RESET: RSET(017)
(017)
RSET
B
B: Bit
CIO, G, A
Operand Data Area
Ladder Symbol
Variations
j
RSET(017)
!
j
RSET(017)
i
RSET(017)
!
i
RSET(017)
!RSET(017)
Description
SET(016) turns the operand bit ON when the execution condition is ON, and
does not affect the status of the operand bit when the execution condition is OFF.
RSET(017) turns the operand bit OFF when the execution condition is ON, and
does not affect the status of the operand bit when the execution condition is OFF.
The operation of SET(016) differs from that of OUT because the OUT instruction
turns the operand bit OFF when its execution condition is OFF. Likewise,
RSET(017) differs from OUT NOT because OUT NOT turns the operand bit ON
when its execution condition is OFF.
The following example shows the operations of the variations of SET(016).
0000
00
0000
00
0000
00
0000
00
0000
00
0000
00
0000
00
0001
05
0001
04
(013)
DIFU 000106
(016)
SET
000103
(016)
j
SET 000102
(016)
i
SET 000101
(016)
SET
000100
000100
000101
000102
000103
000104
000105
000106
000000
Note: Immediate-refresh variations can be used in simplex mode only; they cannot be
used in duplex mode.
Bit Control Instructions
Section 5-7
Summary of Contents for CVM1D
Page 462: ...SYSMAC CVM1D Duplex System Programmable Controllers Operation Manual Revised August 2001...
Page 463: ...iv...
Page 465: ...vi...