![Omron CVM1D Operation Manual Download Page 392](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532392.webp)
ABCĆĆĆĆĆĆĆ123
The last character displayed is just
before “OD” in the message data.
387
If the message data changes while the message is being displayed, the display
will also change.
If not all sixteen words are required for the message, it can be stopped at any
point by inputting “OD.” When OD is encountered in a message, no more words
will be read and the words that normally would be used for the message can be
used for other purposes.
Only the messages whose message number has been preset in the Program-
ming Device will be displayed. If two or more MSG(195) instructions have the
same message number, the earlier message will be replaced when another
MSG(195) instruction with the same message number is executed later.
When a message instruction is executed, its corresponding Message Flag will
be turned ON (bits A09900 to A09907 correspond to messages 0 to 7).
A message instruction can be cleared by executing the instruction with a con-
stant (#0000 to #FFFF) entered for M.
Precautions
N must be BCD between 0000 and 0007.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
N is not between 0 and 7.
Content of
*
DM word is not BCD when set for BCD.
The following example shows the display that would be produced for the instruc-
tion and data given when CIO 000000 is ON. If CIO 000001 goes ON, message
0 will be cleared.
The display message number must be set to 0 in the Programming Device be-
fore executing the instruction.
00000
LD
000000
00001
MSG(195)
#0000
0500
00002
LD
000001
00003
MSG(195)
#0000
#0000
Address Instruction
Operands
(195)
MSG
#0000
0500
(195)
MSG
#0000
#0000
0000
00
0000
01
DM contents
ASCII
equivalent
0500
4
1
4
2
A
B
0501
4
3
4
4
C
D
0502
4
5
4
6
E
F
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
0513
3
1
3
2
1
2
0514
3
3
0
D
3
(end)
0515
3
4
3
5
5
6
xx
Clearing Messages
Example
Network Instructions
Section 5-34
Summary of Contents for CVM1D
Page 462: ...SYSMAC CVM1D Duplex System Programmable Controllers Operation Manual Revised August 2001...
Page 463: ...iv...