CPU Rack
Starting point
Empty slots or Units not
requiring word allocation
(no words allocated)
CPU Unit
Power Supply Unit
Power Supply Unit
Expansion CPU Rack
I/O Control Unit
I/O Interface Unit
Rack #1
Basic I/O Allocation
I/O Word Allocation Example
CPU Rack
Expansion I/O Rack
Expansion I/O Rack
To next rack
Power Supply Unit
DPL
Unit
CPU Unit
Power Supply Unit
CPU Unit
Power Supply Unit
DPL
Unit
Power Supply Unit
CPU Unit
CIO 0000
CIO 0001
CIO 0002 and 0003
CIO 0004
CIO 0005
CIO 0006 and 0007
CIO 0008
CIO 0009
CIO 0010
CIO 001
1
CIO 0012
CIO 0013 and 0014
CIO 0015
Empty (no allocation)
CIO 0016
Power Supply Unit
Power Supply Unit
CIO 0024
CIO 0025
CIO 0026
CIO 0027
CIO 0028
CIO 0029
CIO 0030
CIO 0031
CIO 0032
CIO 0033
Power Supply Unit
Power Supply Unit
Expansion I/O Rack
CIO 0017
CIO 0018
CIO 0019
CIO 0020
CIO 0021
CIO 0022
CIO 0023
Empty (no allocation)
Empty (no allocation)
Empty (no allocation)
Power Supply Unit
Power Supply Unit
Rack #0
Rack #1
Rack #2
Rack #3
Once Units have been mounted and the I/O Table Registration operation has
been performed, a change to any Unit mounted to a Rack that affects the type of
I/O word, or the number of words required by the Unit will cause an I/O verifica-
tion error to occur. This includes adding Units to previously unused slots or re-
moving Units that have already been allocated word(s). A Unit can, however, be
replaced with another Unit that requires the same number of input words and the
same number of output words without generating an I/O verification error.
Dummy I/O Units are available to fill slots for future use or to replace Units that
are no longer needed (see Word Reservations, below).
Rack Changes
CIO (Core I/O) Area
Section 3-3