390
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
Example
The following example is for transmission to a PC through a SYSMAC NET Link
System. When CIO 000000 is ON, the SEND(192) transfers the content of
CIO 0100 through CIO 0104 to D05001 through D05005 of the PC on node 3 of
network 1. The control words also specify that a response is required, use of port
2, 7 retries, and a 10-second response monitoring time.
0
0
0
5
0
0
0
1
0
3
0
0
CIO 0101
CIO 0102
CIO 0103
CIO 0104
CIO 0105
D05001
D05002
D05003
D05004
D05005
D00010
D00011
D00012
15
0
Node 3
(192)
SEND
0101
D05001
D00010
0000
00
Address Instruction
Operands
00000
LD
000000
00001
SEND(192)
0101
D05001
D00010
Control Words
0
2
0
7
0
0
6
4
D00013
D00014
5-34-5 NETWORK RECEIVE: RECV(193)
Variations
j
RECV(193)
(193)
RECV
S
D
C
D: 1
st
destination word CIO, G, A, T, C, DM
C: 1
st
control word
CIO, G, A, T, C, DM
S: 1
st
source word
CIO, G, A, T, C, DM
Operand Data Areas
Ladder Symbol
When the execution condition is OFF, RECV(193) is not executed. When the ex-
ecution condition is ON, RECV(193) transfers data beginning at word S from the
designated PC, BASIC Unit, Personal Computer Unit, or host computer in the
designated node on the SYSMAC NET Link/SYSMAC LINK/Controller Link
System to addresses beginning at D in the PC executing the instruction.
The possible values for S depend on the source Unit. Check the settings for the
Unit. If S is in the EM Area, data will be transferred from the current EM bank in
the source Unit.
The control words, beginning with C, specify the number of words to be received,
the source node, and other parameters. Some control data parameters depend
on whether a transmission is being received in a SYSMAC NET Link, SYSMAC
LINK, or Controller Link System.
Normally a response is required with RECV(193), so set C+3 bit 15 to OFF.
RECV(193) only starts the transmission. Verify that the transmission has been
completed with the Network Status Flags in A502.
Note
1. The node number for the SYSMAC LINK, SYSMAC NET Link, or Controller
Link Unit corresponds to the unit number for the host link interface in the PC
Setup.
2. The execution condition for the up-differentiated variation (
j
RECV(193))
might not be recognized when the mode has been switched from duplex
mode to simplex mode.
Description
Network Instructions
Section 5-34