392
2. Set the BASIC Unit interrupt number when a BASIC Unit is designated.
3. Same as for SYSMAC NET Link Systems. See note 3 above.
4. Values of $01 to $3E indicate nodes 1 to 62. Set to $00 to receive data from
within the local PC. In a Controller Link System, the destination node num-
ber can be set to values of $00 to $20 or $FF.
5. Designates the length of time that the PC retries transmission when bit 15 of
C+3 is OFF and no response is received. The default value is $0000, which
indicates 2 seconds.
6. Transmissions cannot be received from the PC executing RECV(193).
Precautions
C through C+4 must be within the values specified above. To be able use of
RECV(193), the PC must have a SYSMAC NET Link, SYSMAC LINK, or Con-
troller Link Unit mounted.
Do not change the control data during a transmission (i.e., while the correspond-
ing Port Enabled Flag in A502 is OFF).
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
Example
The following example is for receiving from a PC through a SYSMAC NET Link
System. When CIO 000000 is ON, the RECV(193) transfers the content of
CIO 0101 through CIO 0105 of the PC on node 3 of network 1, to D05001
through D05005 of the PC executing RECV(193). The control words also speci-
fy that a response is required, use of port 2, 7 retries, and a 10-second response
monitoring time.
0
0
0
5
0
0
0
1
0
3
0
0
CIO 0101
CIO 0102
CIO 0103
CIO 0104
CIO 0105
D05001
D05002
D05003
D05004
D05005
D00010
D00011
D00012
15
0
Node 3
00000
LD
000000
00001
RECV(193)
0101
D05001
D00010
Address Instruction
Operands
0000
00
(193)
RECV
0101
D05001
D00010
Control Words
0
2
0
7
0
0
6
4
D00013
D00014
5-34-6 DELIVER COMMAND: CMND(194)
Variations
j
CMND(194)
(194)
CMND
S
D
C
D: 1
st
response word
CIO, G, A, T, C, DM
C: 1
st
control word
CIO, G, A, T, C, DM
S: 1
st
command word
CIO, G, A, T, C, DM
Operand Data Areas
Ladder Symbol
When the execution condition is OFF, CMND(194) is not executed. When the
execution condition is ON, CMND(194) transmits the command beginning at
word S to the designated Unit at the destination node number in the designated
network of the SYSMAC NET Link/SYSMAC LINK/Controller Link System, and
receives the response beginning at word D.
Description
Network Instructions
Section 5-34