5-27-4 I/O REFRESH: IORF(184)
(184)
IORF
St
E
E: Ending word
CIO
St: Starting word
CIO
Operand Data Areas
Ladder Symbol
Variations
j
IORF(184)
When the execution condition is OFF, IORF(184) is not executed. When the ex-
ecution condition is ON, all words between St and E will be refreshed. This will be
in addition to the normal I/O refresh performed during the CPU’s scan.
IORF(184) can be used to refresh I/O words on the CPU, Expansion CPU, or
Expansion I/O Racks only. It cannot be used for other I/O words in SYSMAC
BUS or SYSMAC BUS/2 Remote I/O Systems.
St must be less than or equal to E. If St is greater than E, the instruction will be
treated as NOP(000).
St and E must be in the I/O Area, CIO 0000 to CIO 0511.
The up-differentiation (
j
) execution condition might not be recognized when the
PC has been switched from duplex mode to simplex mode.
Note Refer to page 101 for general precautions on operand data areas.
There are no flags affected by this instruction.
Example
When CIO 000000 is ON in the following example, the status of all inputs allo-
cated to bits in words from CIO 0010 through CIO 0014 will be read into memory,
refreshing the status of these input bits.
Address
Instruction
Operands
00000
LD
000000
00001
IORF(184)
0010
0014
5-27-5 I/O DISPLAY: IODP(189)
(189)
IODP
C
S
S: Source word(s)
CIO, G, A, T, C, DM
C: Control word
CIO, G, A, T, C, #, DM, DR, IR
Operand Data Areas
Ladder Symbol
Variations
j
IODP(189)
When the execution condition is OFF, IODP(189) is not executed. When the ex-
ecution condition is ON, IODP(189) outputs four characters to the 7-segment
display on a SYSMAC BUS/2 Remote I/O Slave Unit, I/O Control Unit, or I/O In-
terface Unit. The four characters can be in 7-segment display code in source
words S and S+1, or the content of a single hexadecimal source word (S).
The control word contains information defining the Unit to which the characters
will be output, whether the source data is hexadecimal or 7-segment display,
whether the characters are to flash or not, and whether the display can be con-
trolled from the Unit itself.
Description
Precautions
Flags
Description
Control Word
Special Instructions
Section 5-27